AHU Fan PositionDraw-through vs blow-through arrangement
Drive Type
Motor Enclosure
InstallationAffects System Effect Factor — AMCA 201
SEF — AMCA 201 — In-duct installation. Lowest System Effect — ensure ≥3 duct diameters of straight duct at inlet and outlet. SEF not calculated in this tool. Add to design FSP before final fan selection. Ref: AMCA Publication 201-02.
SEF Addition (AMCA 201)Add to FSP — based on connection velocity pressure
—
Corrected FSP + SEFUse this value for final fan catalogue selection
—
Airfoil (AF)
Best efficiency centrifugal fan. Ideal for AHU and duct systems at 300–1200 Pa. Widest stable operating range. Not suitable for contaminated or sticky airstreams.
Fan Motor Assembly
Live Assembly Preview — updates with selection
AHU Pressure Drop Breakdown
VERIFY FSP — Enter each component's pressure drop. Your FSP input should equal the sum of all components. This helps verify your FSP is complete before fan selection.
Filter Bank ΔPPa — clean; dirty filter ≈ 2× clean value
Cooling Coil ΔPPa — CHWS or DX coil, face velocity ~2.5 m/s
Other Components ΔPPa — heater coil, attenuator, dampers
Total Component FSPCompare to FSP input above
—
Psychrometric Analysis ASHRAE HoF Ch.1 methods · SI internal · IP display aware
Outside Air (OA)
Dry Bulb (°C)
Relative Humidity (%)
Enthalpy est.
—
Return Air (RA)
Dry Bulb (°C)
Relative Humidity (%)
Enthalpy est.
—
AHU Parameters
Fresh Air Fraction (%)OA / Total supply airflow
Target Supply DB (°C)Coil leaving or supply temperature target
Coil Leaving RH (%)Saturated ≈ 90–100%
State Point
DB (°C)
RH (%)
W (g/kg)
h (kJ/kg)
WB (°C)
DP (°C)
Total Coil Dutyṁ × (h_in − h_out)
—
Sensible Loadṁ × Cpa × ΔT
—
Latent LoadTotal − Sensible
—
Sensible Heat RatioSHR = Qs / Qt
—
Coil ΔT
—
Actual Supply Air TempCoil leaving ± fan heat gain
—
Coil Dehumidification
—
Psychrometric chart — state points & process lines · ASHRAE HoF Ch.1
Duty Point
Volume Flow RateL/s
Fan Static Pressure (FSP)Pa — system resistance at design flow (AMCA 210 / ISO 5801)
Air Temperature°C
Site Altitudem
Safety FactorApplied to flow & pressure
Air Densitykg/m³ — ISO 2533
1.190
Density-Corrected Design Duty
Design Flow w/ SF
—
Fan Static Pressure w/ SF
—
Density-Corrected FSPFSP × (1.2 / ρ) — use for fan catalogue
—
Velocity Pressure Pv½ρv² at ~5 m/s duct velocity
—
Fan Total Pressure (FTP)FSP + Pv — AMCA 210
—
Atmospheric PressureISO 2533 altitude correction
—
Air Mass Flowṁ = Q × ρ (kg/s)
—
Fan P-Q Curve & System Characteristic
Hover over chart to inspect values
Operating Point
Run calculation on Fan Duty tab first.
System Characteristic
—
Duct System Resistance Builder Darcy-Weisbach · ε=0.09mm galv. sheet metal · ASHRAE HVAC Handbook
CRITICAL PATH — Add the highest-resistance path only. Include supply and return duct if a draw-through AHU fan. Total ΔP should match your FSP input above.
Type
Description
Parameters
Velocity
Pv (Pa)
ΔP (Pa)
No components added — use the buttons above to build your system resistance.
Total System ΔP
—
FSP Input
—
Difference
—
Advanced System Curve Options static lift · multi-branch index circuit — SMACNA / CIBSE Guide B2
STATIC LIFT / PRESSURISATION (ΔP_static)
WHAT IS THIS — Use when the system has a non-zero pressure at zero flow: kitchen exhaust stack buoyancy, building pressurisation, height difference, or fire stairwell pressurisation. System curve: ΔP = ΔP_static + k·Q²
Static Lift ΔP_static (Pa)
Adjusted ΔP at design Q
—
Static fraction of total
—
Effective system k
—
MULTI-BRANCH INDEX CIRCUIT
INDEX CIRCUIT — The highest-resistance branch. Fan must meet index ΔP. Other branches need balancing dampers to absorb excess pressure.
0 branches
Index Circuit ΔP
—
Total System Flow
—
Add branches to calculate index circuit.
System Curve Data Table
% Flow
Flow (L/s)
System ΔP (Pa)
Fan ΔP (Pa)
Power (kW)
Efficiency (%)
Fan Affinity Laws — Speed Change
Speed Change Calculator
N₁ — Original Speed (%)Reference speed (100% = design)
N₂ — New Speed (%)Target speed to calculate
Q₁ (L/s)
P₁ (Pa)
W₁ — Shaft Power (kW)
New Duty at N₂
Q₂ = Q₁ × (N₂/N₁)
—
P₂ = P₁ × (N₂/N₁)²
—
W₂ = W₁ × (N₂/N₁)³
—
Power Ratio (N₂/N₁)³
—
Power Saving (%)
—
Density Change Calculator
ρ₁ — Original Density (kg/m³)From duty point (auto-filled)
ρ₂ — New Density (kg/m³)Target operating density
Or enter new conditions:
New Altitude (m)
New Temperature (°C)
Density-Corrected Duty
NOTE — Flow is unchanged for density variation. Only pressure and power scale.
P₂ = P₁ × (ρ₂/ρ₁)
—
W₂ = W₁ × (ρ₂/ρ₁)
—
Density Ratio (ρ₂/ρ₁)
—
P-Q CURVE SUPERPOSITION — parametric (indicative)
─ Single fan ─ Combined ─ System curve ● Op. point
CUBE LAW — Power saving at 80% speed = 49% | at 70% speed = 66% | at 60% speed = 78%. VFD control delivers exceptional part-load savings.
Fan Schedule
Add fans from the Fan Duty tab — compare, export, manage your project schedule
No fans scheduled
Set up a fan on the Fan Duty tab, run a calculation, then click + Add to Schedule
#
Tag
Fan Type
Drive
Flow (L/s)
FSP + SEF
Motor
Load %
SFP
Rating
Lw
Status
Actions
—
All values stored in SI — displayed in current unit. Click Load to restore fan inputs.
✓ Fan added to schedule
ESTIMATED DATAAll performance values are calculated from generic fan type models — not manufacturer-measured data. Obtain AMCA 210-certified P-Q curves and AMCA 300-certified sound power data from the manufacturer before procurement. SEF and acoustic values are indicative only.
—
Design Flow
L/s
—
Total SP
Pa
—
Shaft Power
kW
—
Fan Efficiency
%
—
SFP W/[L/s]
Fan Performance Rating AMCA 205 efficiency class · FEI estimate · operating confidence
FAN EFFICIENCY
Efficiency RangeTypical for type
—
AMCA 205 ClassFan Energy Grade
—
FEI (indicative)AMCA 208 estimate
—
Motor IE ClassIEC 60034-30-1
—
OPERATING CONFIDENCE
PARAMETRIC MODEL — Efficiency values are indicative (±10–15%). Obtain AMCA 210-certified manufacturer data before final equipment specification.
Dominant Octave BandHighest A-weighted band — target for attenuation
—
Fan Heat Rise (impeller)ΔT through fan wheel — motor-in-stream adds more
—
Octave band Lw — indicative per ASHRAE HoF Ch.49 / AMCA 300. Obtain AMCA-certified data from manufacturer.
Vibration Isolation
Isolation Type
—
Static Deflection
—
Balance GradeISO 14694:2003 — fan balance quality
—
Vibration LimitISO 20816-3 — velocity RMS at bearing housing
—
Wheel Diameter est.Indicative — confirm with manufacturer
—
Bearing Life & Vibration Isolation ISO 281 · ISO 20816-3 · ASHRAE HoF Ch.48
BEARING LIFE — ISO 281
Estimated Speed
—
Bearing Dyn. Load C
—
Shaft Load P
—
C/P Ratio
—
L10 Life (hrs)
—
L10 (years)
—
Maintenance Interval
—
VIBRATION ISOLATION DESIGN
Mount Type
Operating Freq (Hz)
—
Isolator fn (Hz)
—
Static Deflection δ
—
Freq Ratio r = f/fn
—
Transmissibility Tr
—
Isolation Efficiency
—
TRANSMISSIBILITY CURVE
─ Transmissibility vs r=f/fn
● Operating point
Inertia Base Rec.
—
Flexible Conn. Req.
—
Duct Acoustic Attenuation Path ASHRAE HoF Ch.48 — fan Lw through ductwork to grille
HOW TO USE — Build the duct path from fan outlet to grille.
Add components in order: straight sections, elbows, branches, lined sections, end reflection.
The resulting Lw at grille feeds directly into Room Acoustic Analysis below.
0 components
OCTAVE BAND ATTENUATION SUMMARY (dB)
Component
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Total IL
FAN Lw AT OUTLET
—
A-weighted dB(A)
Lw AT GRILLE ↓ Room
—
A-weighted dB(A) — feeds Room Acoustic Analysis
No path components added — room acoustics uses raw fan Lw.
NOTE — This analysis treats fan Lw as if radiated from the supply diffuser(s). In practice, apply duct insertion loss before this step. Obtain AMCA-certified octave-band data for final acoustic design.
Room Dimensions
Length (m)
Width (m)
Height (m)
Volume / Surface
—
Acoustic Properties
Room Type
Noise Standard
Avg absorption ᾱ
—
Room constant RS·ᾱ/(1−ᾱ) — Sabine, m²
—
RT60Reverberation time — Sabine eq.
—
Source / Receiver
Directivity Q
Distance to receiver (m)
Target space
Critical distanceWhere direct = reverberant field
—
Band
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Total
Lp at receiverA-weighted sound pressure level
—
Estimated NC ratingLowest NC curve not exceeded
—
Compliance
—
Direct field levelQ/(4πr²) component
—
Reverberant field level4/R component
—
Field type
—
Octave band Lw vs Lp at receiver vs NC target — ASHRAE HoF Ch.48
Commissioning Checklist Site engineer reference — ISO 14694 · AS/NZS 3000 · manufacturer data takes precedence
Pre-Start Checks
Run calculation first.
Motor & Starter Settings
—
Acceptance Criteria
—
Drive Settings
—
Checks & Warnings
PRONeed a built-in fan manufacturer database, multi-fan schedule, or branded PDF submittals? — Upgrade to DENOVA Fan Selector Pro
Status:✓ Acceptable
DENOVA
Fan Selector
LITEv2.1
Project: —
Number: —
Fan Tag: —
By: —
Date: —
✓ Acceptable
1. Fan Selection Summary
Duty Inputs
Fan Type
—
Application
—
Drive Type
—
Motor Enclosure
—
AHU Fan Position
—
Design Flow
—
Total Static Pressure
—
Air Temperature
—
Altitude
—
Air Density
—
Safety Factor
—
Calculated Results
Design Flow w/ SF
—
Design Pressure w/ SF
—
Shaft Power
—
Fan Efficiency
—
Motor Input Power
—
Recommended Motor
—
Motor Loading
—
Estimated FLC
—
SFP
—
SFP Rating
—
ASHRAE 90.1 FPL
—
EU ErP MEI
—
EN 13779 SFP Cat.
—
Region / Frequency
—
2. System Curve
% Flow
Flow (L/s)
Flow (m³/s)
System ΔP (Pa)
Fan ΔP (Pa)
Power (kW)
Efficiency (%)
3. Motor & Electrical
Motor Sizing
Shaft Power
—
Drive Loss
—
Motor Input Power
—
Motor Efficiency est.
—
Recommended Motor (kW)
—
IE Efficiency Class
—
Motor Frame (IEC)
—
Motor Loading
—
Electrical — Ref: AS/NZS 3000:2018
Supply Voltage
—
Phase
—
Estimated FLC
—
Locked Rotor Current
—
Starting Method
—
Circuit Breaker
—
Cable Size est.
—
4. SFP, SEF, Pressure, Noise & Vibration
Energy & Pressure
Fan Static Pressure (FSP)
—
Velocity Pressure Pv
—
Fan Total Pressure (FTP)
—
SFP
—
SFP Rating
—
Annual Energy est.
—
Fan Heat Rise (impeller)
—
SEF — System Effect (AMCA 201)
Inlet Connection
—
Outlet Connection
—
SEF Addition
—
Corrected FSP + SEF
—
Use corrected FSP for final fan catalogue selection
Noise & Vibration
Sound Power Lw (A-weighted)
—
Blade Pass Frequency
—
Dominant Octave Band
—
Test Method Ref
AMCA 300-14 / ASHRAE HoF Ch.49
Isolation Type
—
Static Deflection
—
Balance Grade
—
Vibration Limit
—
Wheel Diameter est.
—
AHU Pressure Drop Breakdown
Filter Bank ΔP
—
Cooling Coil ΔP
—
Duct System ΔP
—
Terminals / Diffusers ΔP
—
Other Components ΔP
—
Total Component FSP
—
Octave Band Sound Power — Lw (dB re 1pW) — ASHRAE HoF Ch.49 / AMCA 300 indicative
Band
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Lw (dB)
—
—
—
—
—
—
—
—
Lw(A) (dB)
—
—
—
—
—
—
—
—
5. Checks & Warnings
6. Psychrometric Analysis ASHRAE HoF Ch.1 · AHU coil duty
State Point
DB
RH (%)
W (g/kg)
h (kJ/kg)
Coil Duty
Total Cooling Load
—
Sensible Load
—
Latent Load
—
Sensible Heat Ratio
—
Coil ΔT
—
Supply Air Temperature
—
OA Fraction
—
7. Fan Schedule Project fan list
#
Tag
Fan Type
Drive
Flow (L/s)
FSP+SEF (Pa)
Motor (kW)
Load %
SFP
NC Rating
Status
8. Motor Starting Analysis AS/NZS 3000:2018 · indicative
Starting Method
—
Starting Current (peak)
—
Inrush Multiple
—
Starting kVA Demand
—
Acceleration Time est.
—
9. Duct System Resistance Darcy-Weisbach · critical path
ASHRAE HoF Ch.49 — HVAC fan noise prediction methods
AMCA 210-16 — Fan aerodynamic performance testing
AMCA 300-14 — Fan sound power testing (reverberant room)
AMCA 301-14 — Fan sound rating calculation method
AMCA Publication 201-02 — Fans & Systems (SEF, affinity laws)
ISO 5801:2017 — Fan performance testing (metric)
ISO 2533:1975 — Standard atmosphere / air density
ISO 14694:2003 — Fan balance quality & vibration levels
ISO 20816-3 — Machine vibration evaluation
IEC 60034-30-1:2014 — Motor efficiency classes IE1–IE4
AS/NZS 3000:2018 — Wiring Rules
AS/NZS 3008.1 — Cable current ratings
AS 1668.1 — Smoke exhaust systems
AS 1668.2 — Mechanical ventilation
AS/NZS 1269.1 — Occupational noise management
NCC 2022 Section J — Energy efficiency (SFP benchmarks)
ASHRAE 90.1 — Energy standard for buildings
CIBSE TM54 — SFP evaluation methodology
Terms, Disclaimer & Intellectual Property
DISCLAIMER
All outputs are advisory estimates suitable for concept-stage and tender-stage design only. Fan selections, duty points, sound levels, vibration analysis, motor sizing, and cable sizes must be verified by a qualified engineer using manufacturer-certified performance data before procurement, fabrication, or installation. DENOVA Systems makes no warranty as to the accuracy, completeness, or fitness-for-purpose of any output. Use is at the user's discretion and risk.
CALCULATION BASIS
Public-domain engineering equations only — affinity laws (Stepanoff 1948), Euler turbomachinery equations, ISA atmosphere model, AMCA 201 system effect methodology, ISO 5801 fan performance test conventions. Octave-band acoustics use ASHRAE Ch.48 simplified attenuation formulas with ANSI S12.2 NC curves. Magnus formula for psychrometrics. Vibration limits per ISO 14694 + ISO 20816-3. Cable sizing per AS/NZS 3008.1, IEC 60364, NEC 310.16 tables.
STANDARDS REFERENCE
References cited (AMCA, ASHRAE, ISO, IEC, AS/NZS, NCC, CIBSE, ERP, NEMA) are publications by their respective copyright holders. DENOVA Fan Selector cites these by name only as reference publications; it does not reproduce copyrighted text, figures, proprietary tables, or licensed datasets from any cited standard.
DATA HANDLING
No telemetry. No analytics. No external API calls at runtime. Project data does not leave the user's browser. CDN scripts (jsPDF) and Google Fonts are fetched at first load only; both are licensed under permissive open-source terms (MIT / SIL OFL).
TRADEMARKS
DENOVA and the DENOVA wordmark are trademarks of DENOVA Systems. AMCA, ASHRAE, ISO, IEC, NEMA and other organisation names are trademarks of their respective bodies. All other trademarks are acknowledged as the property of their respective owners.
DENOVA·denova.systems·Practical Engineering Software·Confidential where applicable
DENOVA LITE — NOT FOR CONSTRUCTION
1. Fan Type Guide▾
Type
Typical η
Flow Range
Pressure Range
Best Application
Avoid When
Centrifugal AF
78–85%
Any
300–1500 Pa
AHU, clean duct systems
Contaminated/sticky air
Centrifugal BC
70–80%
Any
100–1200 Pa
General ventilation, AHU
Very high pressure (>1200Pa)
Centrifugal FC
55–65%
High flow
50–750 Pa
Low static, high volume
High pressure duties
Axial Vaneaxial
70–82%
High flow
150–600 Pa
In-duct, car parks
Very low/high flow (stall risk)
Axial Tubeaxial
60–72%
High flow
50–400 Pa
General duct exhaust
High pressure, dirty air
Axial Propeller
45–55%
Very high
0–200 Pa
Roof exhaust, free air
Ducted systems >200 Pa
Plug Fan / EC
75–85%
Any
200–1200 Pa
AHU plenum, data centres
Contaminated air, high temp
Mixed Flow
68–78%
High flow
100–600 Pa
Inline duct, car parks
Very high pressure
2. Fan Laws (Affinity Laws)▾
The fan affinity laws describe how flow, pressure, and power scale with speed at the same system resistance. They are valid for a given fan operating on the same system curve.
VFD CUBE LAW — Reducing fan speed by just 20% (to 80%) cuts power consumption by 49%. Reducing to 60% speed cuts power by 78%. This is why VFDs are standard on variable-flow systems.
LIMITATION — Affinity laws are valid only on the same system curve. For different system resistances, use the full P-Q curve intersection method.
DENSITY — For altitude or temperature changes, flow is unchanged. Only pressure and power scale with density ratio. Fan speed and physical geometry are unchanged.
4. AMCA & Standards Reference▾
Standard
Title
Application in This Tool
AMCA 210-16
Laboratory Methods of Testing Fans for Aerodynamic Performance Rating
Primary certification for fan P-Q curves. Specify AMCA 210 certified fans.
AMCA 300-14
Reverberant Room Method for Sound Testing of Fans
Basis for fan sound power (Lw) data. Noise estimates in tool are indicative only.
AMCA 301-14
Methods for Calculating Fan Sound Ratings from Laboratory Test Data
Calculation method for manufacturer-published acoustic data.
AMCA Pub 201-02
Fans and Systems — Application Guide
Affinity laws, System Effect Factors (SEF), duct connection guidelines. SEF not calculated in this tool — must be added to system resistance manually.
AMCA 99-16
Standards Handbook — Fan Terminology & Definitions
Fan type definitions, pressure terminology (FSP, FTP, FVP).
ISO 5801:2017
Industrial Fans — Performance Testing (metric equivalent of AMCA 210)
International metric standard for fan P-Q curve testing.
ISO 2533:1975
Standard Atmosphere
Air density calculation from altitude and temperature. Used throughout this tool.
Balance grade G2.5 (precision) / G6.3 (normal). Vibration limit basis for this tool.
ISO 20816-3
Mechanical Vibration — Evaluation of Machine Vibration
Bearing housing vibration velocity limits. Zone A/B/C/D classification.
IEC 60034-30-1:2014
Rotating Electrical Machines — Motor Efficiency Classes
IE1 / IE2 / IE3 / IE4 efficiency classes. IE3 is minimum in most jurisdictions.
AS/NZS 3000:2018
Wiring Rules
Governs cable sizing, circuit protection, isolation. All electrical outputs in this tool are indicative — verify with licensed electrician.
AS/NZS 3008.1
Electrical Installations — Selection of Cables
Cable current rating tables with derating for ambient temperature, grouping and installation method.
AS 1668.1
The Use of Ventilation and Air Conditioning — Smoke Control
Smoke exhaust fan requirements including high-temperature motor ratings (300°C/2hr or 400°C/2hr).
AS 1668.2
The Use of Ventilation and Air Conditioning — Mechanical Ventilation
General mechanical ventilation requirements for buildings in Australia.
AS/NZS 1269.1
Occupational Noise Management — Measurement and Assessment
Noise assessment methodology. Note: fan Lw (sound power) ≠ Lp (sound pressure at receiver).
NCC 2022 Sect. J
National Construction Code — Energy Efficiency
SFP limits for HVAC fan systems. Benchmarks A+ through E used in this tool.
ASHRAE 90.1
Energy Standard for Buildings
US energy benchmark reference. SFP limits comparable to NCC Section J.
CIBSE TM54
Evaluating Operational Energy Performance
SFP methodology and A/B/C/D rating scale used in this tool.
CRITICAL — SYSTEM EFFECT (AMCA 201) — Fan performance curves (AMCA 210) are tested under ideal laboratory conditions. In real installations, non-ideal connections at the fan inlet or outlet create additional pressure losses called System Effect Factors (SEF). Common causes: elbow directly at fan inlet, duct area change immediately at discharge, insufficient straight duct length. SEF can range from 15–100+ Pa depending on installation. Always add SEF to system resistance before selecting the fan. Refer to AMCA Publication 201-02 Table 8 for SEF values by installation type.
FSP vs FTP vs FVP (AMCA 99) — Fan Static Pressure (FSP) = pressure rise available to overcome system resistance. Fan Total Pressure (FTP) = FSP + outlet velocity pressure. Fan Velocity Pressure (FVP) = ½ρv² at fan outlet. This tool uses FSP as the primary duty input, consistent with HVAC duct system design practice. Ensure manufacturer data is also stated as FSP when comparing.
IE3 MOTOR REQUIREMENT — IEC 60034-30-1:2014 defines IE efficiency classes. Most Australian jurisdictions (GEMS Determination) mandate IE3 minimum for motors 0.75–375 kW on continuous duty. Specify IE3 or IE4 on all fan motor schedules. Plug fans with EC motors typically achieve IE4+ equivalent.
Rating
SFP W/(L/s)
Description
Standard Reference
A+
≤ 0.5
Excellent — high efficiency selection
CIBSE TM54 / Beyond NCC
A
≤ 0.8
Good — efficient selection
CIBSE TM54
B
≤ 1.25
Acceptable — meets best practice
NCC 2022 Section J / ASHRAE 90.1
C
≤ 1.8
Below average — review selection
NCC 2022 minimum
D
≤ 2.5
Poor — redesign recommended
Fails NCC 2022
E
> 2.5
Unacceptable — non-compliant
Fails NCC 2022 & ASHRAE 90.1
NCC 2022 — Section J Part J6 sets maximum SFP for HVAC fan systems. Values shown are for supply fans in comfort systems. Different limits apply to exhaust, kitchen and industrial systems. Always verify with the applicable edition of NCC for your jurisdiction.
5. Fan Type Comparison — Current Duty▾
HOW TO USE — Run a fan calculation first, then this table compares all fan types at the same duty. Useful for selecting the best type for your application.
Fan Type
η BEP
η Range
Shaft (kW)
Motor
SFP
Lw(A)
AMCA
Overload
Stall Q
Run a calculation to populate this comparison
6. VFD Power Quality — AS 61000-3-12 Reference▾
HARMONIC LIMITS — AS/NZS 61000-3-12:2015
Harmonic Order
Max Current THD (%)
Risk Level
VFD input <15kW
≤16% Ithd
Low
VFD input 15-75kW
≤12% Ithd
Moderate
VFD input >75kW
≤8% Ithd
High — harmonic filter required
Mitigation: Line reactor (5% impedance), passive LC filter, active front end (AFE) drive, or 12/18-pulse transformer for large drives >75kW.
CURRENT SYSTEM — VFD ASSESSMENT
Run a calculation with VFD drive type to see harmonic assessment.
Input Power Factor (fundamental): Typical 6-pulse VFD PF ≈ 0.85-0.95 at full load, degrades at part-load. With AFE: PF ≈ 0.99.
AS 61000-3-12 Scope: Applies to equipment with input current per phase >16A. For <16A see AS 61000-3-2.